NOVEC1230 Fire Suppression System With No Contamination Of Storage Rooms Using Noncorrosive With UL Certification
Description of UL NOVEC1230 container
-- Attributes of Welded Steel GB series container
Material |
HP345 |
|
Carbon: |
≤0.20% |
|
Manganese: |
≤1.50% |
|
Silicon: |
≤0.35% |
|
Phosphorus: |
≤0.025% |
|
Sulphur: |
≤0.015% |
|
Aluminium acid-soluble: |
≥0.015 |
|
Nominal Working Pressure |
53 bar |
|
Hydrostatic Test Pressure |
80 bar |
|
Work Temperature |
0 °C ~ 50 °C |
|
Paint Specification |
Red Polyester Powder Coated |
|
Certification |
GB |
-- FK-5-1-12 (NOVEC1230) Welded Container Assembly Details : GB Container
Cylinder with Valve Assembly Part No. |
Container Assembly Type |
Nominal Working Pressure (bar) |
Nominal Cylinder Volume
(L) |
Fill Capacity (kg) |
Outlet Size (mm) |
Empty Weight (kg) |
|
Min. |
Max. |
||||||
813.101.0455 |
AG5112SPA-40 |
25 |
40 |
19.2 |
44.4 |
33 |
41 |
813.101.0465 |
AG5112SPA-50 |
50 |
24.0 |
55.5 |
33 |
52 |
|
813.101.0475 |
AG5112SPA-60 |
60 |
28.8 |
66.6 |
33 |
59 |
|
813.101.0486 |
AG5112SPA-70 |
70 |
60 |
77.7 |
49 |
72 |
|
813.101.0496 |
AG5112SPA-80 |
80 |
60 |
88.8 |
49 |
80 |
|
813.101.0506 |
AG5112SPA-90 |
90 |
60 |
99.9 |
49 |
94 |
|
813.101.0516 |
AG5112SPA-100 |
100 |
60 |
111 |
49 |
100 |
|
813.101.0526 |
AG5112SPA-120 |
120 |
60 |
133.2 |
49 |
113 |
|
813.101.0536 |
AG5112SPA-140 |
140 |
67.2 |
155.4 |
49 |
107 |
|
813.101.0546 |
AG5112SPA-150 |
150 |
72.0 |
166.5 |
49 |
134 |
|
813.101.0566 |
AG5112SPA-170 |
170 |
81.6 |
188.7 |
49 |
124 |
|
813.101.0576 |
AG5112SPA-180 |
180 |
86.4 |
199.8 |
49 |
130 |
|
813.101.0455 |
AG5112SPA-40 |
42 |
40 |
19.2 |
44.4 |
33 |
41 |
813.101.0465 |
AG5112SPA-50 |
50 |
24.0 |
55.5 |
33 |
52 |
|
813.101.0475 |
AG5112SPA-60 |
60 |
28.8 |
66.6 |
33 |
59 |
|
813.101.0485 |
AG5112SPA-70 |
70 |
60 |
77.7 |
49 |
72 |
|
813.101.0495 |
AG5112SPA-80 |
80 |
60 |
88.8 |
49 |
80 |
|
813.101.0505 |
AG5112SPA-90 |
90 |
60 |
99.9 |
49 |
94 |
|
813.101.0518 |
AG5112SPA-100 |
100 |
60 |
111 |
49 |
100 |
|
813.101.0528 |
AG5112SPA-120 |
120 |
60 |
133.2 |
49 |
113 |
|
813.101.0538 |
AG5112SPA-140 |
140 |
67.2 |
155.4 |
49 |
107 |
|
813.101.0548 |
AG5112SPA-150 |
150 |
72.0 |
166.5 |
49 |
134 |
|
813.101.0568 |
AG5112SPA-170 |
170 |
81.6 |
188.7 |
49 |
149 |
|
813.101.0578 |
AG5112SPA-180 |
180 |
86.4 |
199.8 |
49 |
130 |
Description of UL NOVEC1230 Fire Suppression System
FK-5-1-12, like halon, extinguishes by causing a chemical reaction with the combustion products, and does not remove oxygen like CO2 and other inert agents.
Therefore, exposure to FK-5-1-12 at the design concentration of 4.5% (Class A and Class C Minimum Design Concentration) and 5.85% (Class B Minimum Design Concentration) is not hazardous to health. FK-5-1-12 systems for spaces that are normally occupied and designed to concentrations up to the NOAEL (10%) shall be permitted, but maximum exposure shall not exceed than 5 min. Exposure to higher concentrations is permissible for limited periods. Refer to NFPA 2001 Section "Safety" for exposure requirements. As with halons, the US EPA and the National Fire Protection Association (NFPA) recommend that unnecessary exposure to any agent be avoided and that personnel evacuate protected areas as quickly as possible to avoid the decomposition products of the fire.
Components of UL NOVEC1230 Fire Suppression System
No. |
Part Name |
No. |
Part Name |
1 |
Cylinder |
7 |
Pilot Hose |
2 |
Mounting Bracket |
8 |
Pneumatic Actuator |
3 |
Fix Steel Channel |
9 |
Bleed Valve |
4 |
Container Valve |
10 |
Discharge Pressure Switch |
5 |
Electrical Actuator |
11 |
Nozzle |
6 |
Valve Outlet Adaptor |
|
|
Features of UL NOVEC1230 Fire Suppression System
FK-5-1-12 is a clean agent containing no particles or oily residues. It is produced under ISO 9001 guidelines to strict manufacturing specifications ensuring product purity. FK-5-1-12 leaves no residue or oily deposits on delicate electronic equipment, and can be removed from the protected space by ventilation.
FK-5-1-12 is a liquid at room temperature with a low vapor pressure, which allows for ease in handling, storage, and shipping. FK-5-1-12 is thermally and chemically stable, zero ozone depletion potential, atmospheric lifetime of five days only. It has unique qualities that provide the right balance of fire extinguishing performance,end use safety,and environmental sustainability.
Application of UL NOVEC1230 Fire Suppression System
üComputer room, communication room, power distribution room, library, archives, Museum, etc.
ü Be used for electrical fire, liquid fire, solid fire, gas fire which can be cut off the gas source before extinguishing occur, etc.
Packages of UL NOVEC1230 Fire Suppression System
We always pack it with polyfoam firstly and then put it into a wooden case. Sometimes, in order to meet with customers or the safety requirement, we will make a pallet for the goods.